Protection coordination study

When a fault occurs, only the nearest protection should trip, and fast enough for the equipment to withstand it.

We check protection coordination (selectivity) in the worst-case configuration, with maximum and minimum short-circuit currents and maximum load current. A single calculation case is not enough.

Four types of discrimination exist and are often combined. Current discrimination relies on thresholds, time discrimination on time delays, typically 250 to 300 ms between stages. With logic discrimination, the downstream protection blocks the upstream one. Differential protection monitors a closed zone and operates instantaneously.

Earth faults are treated separately. Their current depends on the neutral earthing arrangement and is sometimes too low for conventional functions. We check the current transformers at the same time, because a saturating CT distorts every calculated time.

01What we do

Method

  • Maximum and minimum fault currents
  • Time-current curves per protection chain
  • Current, time and logic discrimination
  • Verification of current transformer performance

Results

  • Deviations found and corrections
  • Proposed settings
  • Curves per voltage level

02Examples

Time-current curves of two cascaded protections, 250 ms margin at maximum short-circuit current1001 00010 00020 0000.010.1110100Current (A, referred to 20 kV)Time (s)Isc max 8 kAP2 · MV feederIs 200 A · TMS 0.10P1 · TR incomerIs 400 A · TMS 0.30Δt = 250 ms
Fig. 01Two cascaded protections (IEC 60255, inverse curve), with a 250 ms margin at the maximum short-circuit current.Worked example
Time-current curves plotted in ETAP
Fig. 02Protection coordination curves plotted in ETAP.Anonymised deliverable

03Our offer

Usual content of an offer for this type of assignment. The exact scope, deliverables and price are set in the quotation.

  1. Package 1Data and fault currents

    Maximum and minimum currents, three-phase and earth, per busbar.

  2. Package 2Protection chains

    Relays, CTs and settings, from feeder to incomer.

  3. Package 3Time-current curves

    Margins at the critical points, CT verification.

  4. Package 4Proposed settings

    Justified corrections and updated settings schedule.

04How we work

  1. 01Fault currents

    Maximum and minimum, three-phase and earth, per busbar.

  2. 02Protection chains

    From feeder to incomer, each relay and its CT.

  3. 03Time-current curves

    Margins measured at the critical points.

  4. 04Settings

    Proposed corrections, updated settings schedule.

05References

Industrial site

Protection coordination and relay verification

MV protection coordination and on-site check of the settings.

General contractor

Protection plan, 240 MVA data centre

Selection of protection functions, current transformer sizing, settings, follow-up of testing through to commissioning.

All references

06Frequently asked questions

Protection coordination or protection plan?

Coordination checks that the settings work together. The protection plan goes further and also covers the choice of functions and current transformers, as well as the settings schedule.

Do you check the settings actually in place?

Yes, on site with our injection test sets (see Protection, tap changer and automation testing).

07See also

For a project, give us the voltage, power, location and deadline in a few lines.
Reply within 48 working hours.

Write to LDHT