Data centre, Île-de-France
Load flow campaign on an ETAP model
Audit of the existing scenarios and sweep of upstream voltage × configurations. The on-load tap changer range of the 225 kV transformers proved insufficient.
Study
Voltages, loading and losses calculated in every operating configuration, nominal and degraded.
We calculate the voltage plan in every relevant operating configuration to find the worst case: minimum and maximum upstream voltage, outages, bus coupler positions, tap changer positions, maximum and minimum load.
Minimum load needs as much attention as maximum load. At no load, MV cables generate reactive power and the voltage rises, and the need for a shunt reactor or a limit on the tap changer often appears in this case.
These campaigns are run with in-house scripts for ETAP and PowerFactory. The script discovers the network, checks the busbars and produces a result per scenario. The assumptions are written down and the model is delivered to you.
Usual content of an offer for this type of assignment. The exact scope, deliverables and price are set in the quotation.
Data list, deviations found, assumptions agreed with you before calculation.
ETAP or PowerFactory model, or takeover of yours after a check.
Scenario matrix set in the quotation: upstream voltage, N and N-1 configurations, maximum and minimum load, tap changer positions.
Results per scenario, deviations from criteria, conclusions and recommendations.
Presentation of the results and incorporation of your comments.
Impedances, nameplates, lengths, with a source for every value.
Upstream voltage × configuration × load × tap.
Out-of-range voltages, overloads, losses, reactive power at the point of delivery.
Required tap changer range, compensation, operating limits.
Data centre, Île-de-France
Audit of the existing scenarios and sweep of upstream voltage × configurations. The on-load tap changer range of the 225 kV transformers proved insufficient.
Integrator, West Africa
Load flow, short-circuit, neutral earthing, earthing, stability and protection plan for each plant.
As many as needed to find the worst case, combining upstream voltages, N-1, coupling arrangements and tap changers. The scope is set in the quotation.
Yes, after a check of the model, quoted separately.
For a project, give us the voltage, power, location and deadline in a few lines.
Reply within 48 working hours.