Storage plant connected at 225 kV
EMT study method in PowerFactory
Grid-following and grid-forming inverter models, study cases defined according to CIGRE publications.
Study
Phenomena lasting a few milliseconds, such as inverter response, energisation or switching overvoltages, require a time-domain simulation.
A load flow or a stability study works on averaged quantities. The peak of an inrush current, the response of an inverter to a voltage dip or a resonance between two plants do not appear in them.
EMT solves the network equations step by step, at microsecond scale, representing inductances, capacitances, transformer saturation and inverter control. The result depends directly on the quality of the models, so we always start by checking the models supplied by the manufacturers.
European network operators are preparing requirements for grid-forming inverters. Demand for this type of study will grow, especially for storage.
The calculated overvoltages are also used for insulation coordination to IEC 60071, to select and locate surge arresters and to check the margins between the protection level and the equipment withstand.
Usual content of an offer for this type of assignment. The exact scope, deliverables and price are set in the quotation.
Phenomena studied, cases, criteria, configurations.
Simple tests of the manufacturer models before use, check report.
Cases defined in the quotation, sensitivities on uncertain parameters.
Annotated results, comparison with criteria, recommendations.
Phenomena to study, criteria, configurations.
Simple tests of the manufacturer models before any use.
Defined cases, sensitivities on uncertain parameters.
Settings, equipment (reactors, pre-insertion resistors, surge arresters).
Storage plant connected at 225 kV
Grid-following and grid-forming inverter models, study cases defined according to CIGRE publications.
Wind farm owner
Technical notes on cable joint failures and switching overvoltages, responses to the opposing party's submissions (dires).
Generating substation
Analysis of SCADA logs, identification of control hunting and projection of circuit-breaker wear.